| Model |
OLS2000ERT2U |
| Capacity (VA/W) |
2000VA / 1800W |
| Typology |
Online (Double Conversion) |
| Energy-Saving Technology |
Yes, ECO Mode Efficiency > 95% |
| Input |
| Input Type |
IEC C20 |
| Frequency Range |
40~70Hz |
| Output |
| UPS Outlets (Numbers) |
(4+4) IEC C13 |
| On Battery Output Voltage |
Pure Sine Wave at 208, 220, 230, 240 Vac (Configurable) |
| On Battery Output Voltage Distortion (@Nominal Battery Voltage) |
≤ 3% (Linear Load), ≤ 5%(Non-Linear Load) |
| On Battery Output Frequency |
50 Hz/ 60 Hz (Auto-Sensing or Configurable) ± 0.5% |
| Transfer Time (Typical) |
0ms |
| Overload Protection |
AC Mode: Warning only @ 110%>Load>105%, Transfer to bypass after 60sec @ 120%>Load>110%, Transfer to bypass immediately@ Load>120%
Battery Mode: Warning only @ 110%>Load>105%, Shutdown after 10sec @ 120%>Load>110%, Shutdown immediately @ Load>120 |
| Short Circuit Protection |
UPS Output Cut off Immediately or Circuit Breaker Protection |
| Surge Protection and Filtering |
| Surge Protection |
Yes |
| DSL/Phone/Fax/Modem protection |
RJ11/RJ45 (One In/One Out) |
| Battery |
| Sealed Maintenance Free Lead Acid Battery |
(6) 12V / 7AH |
| Typical Recharge Time |
5 |
| Runtimes |
| Half load-Full load (mins) |
16/6 |
| Status Indication |
| Indicators |
Power On, Line Mode, Battery Mode, Bypass Mode, ECO Mode,C/F Mode, Fault, Replace Battery |
| Audible Alarms |
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery |
| Communication |
| Power Management Software |
PowerPanel® Business Edition |
| Management |
| Self-Test |
Yes |
| Auto-Charge/Auto-Restart |
Yes |
| Auto-Overload Recovery |
Yes |
| Cold Start(DC Start) |
Yes |
| Connectivity Ports |
(1) Serial Port (RS232), (1) USB Port, (1) EPO/ROO |
| SNMP/HTTP Capable |
Optional |
| Dimensions |
88 x 438 x 610 mm |